If you could apply only one idea from the ISA/IEC 62443 series, it should be this one: divide the plant into zones and control every communication between them through conduits. It is the starting point of the part 3-2 risk assessment and the foundation for every technical requirement that follows.
What zones and conduits are
A zone is a group of physical or logical assets that share the same security requirements. It does not have to match a network or a VLAN: it is a design decision based on risk.
A conduit groups the communication channels that connect two or more zones and share security requirements. A conduit is not just a cable or a firewall: it includes the protocols that cross it, who initiates them and how they are protected.
Each zone gets a target security level (SL-T), from 1 to 4, describing what kind of attacker it must withstand: from casual or accidental violation up to a sophisticated, well-resourced attack.
How to partition a plant, step by step
- Define the system under consideration. Draw the boundary: what is inside (PLCs, SCADA, historians, engineering workstations) and which connections leave it. Without a clear boundary, the analysis never ends.
- Inventory assets and communications. A list of devices is not enough; you need to know who talks to whom, over which protocol and why. Passive traffic capture usually reveals connections nobody remembered.
- Run an initial risk assessment. Identify the consequences of losing each part of the system: people's safety, the environment, production or quality.
- Group into zones. At minimum, separate corporate from industrial, safety instrumented systems (SIS) from process control, and anything reachable from outside, such as remote access, into its own zone.
- Draw the conduits. Every flow between zones must go through a documented conduit. Anything without a conduit should not exist.
- Assign an SL-T to each zone and conduit. Then compare it with the level actually achieved today (SL-A). The difference is your work plan.
Common first-time mistakes
Copying the Purdue model without thinking
The reference model levels help you organise, but a zone does not have to be a whole level. Two production lines with different risks can be different zones on the same level.
Making zones too big
One zone for the whole plant limits nothing: an attacker who gets in reaches everything. A hundred zones are not manageable either. Balance risk against upkeep.
Forgetting third-party access
The integrator's remote access, the maintenance technician's laptop or a vendor's modem are conduits too, and often the weakest ones.
Documenting it once and never again
The zones-and-conduits diagram must be updated with every change to the plant. Otherwise, a year from now it will describe an installation that no longer exists.
Where to start tomorrow
Pick a bounded area, such as one production line, and run the whole process at small scale. You will learn more than from a theoretical analysis of the entire plant, and you will have a result to show management.